1.5 —— Suction diameter(mm)divided by 25 , and then change the Value into integer
G —— Boiler feed pump
C —— Indicating type of te pump
J —— Mechanical seals
5 —— Specific speed divided by 10 (i.e.the specific speed of the pump is 50)
6 —— Number of impellers
No.of stag | Rate of fbw | Totalead H(m) | Rotating speed r(rpm) | Fower (kw) | Eiciency n(%) | Permisible suton head Hs(m) | OD.of impeler (mm) | ||
m*hr | 1Sec | Shhaft power | Moterpower | ||||||
2 3 4 5 6 7 8 9 | 6 6 6 6 6 6 6 6 | 166 166 166 166 166 166 166 166 | 46 2 92 115 138 L 184 207 | 2950 2950 2950 2950 2950 2950 2950 2950 | 2 3 4 5 6 7 8 9 | 3 4 55 75 75 75 11 15 | 38 38 38 38 38 38 38 38 | 65 65 65 65 65 65 65 65 | 136 136 136 136 136 136 136 136 |
1 、 Sleeve nut | 2 、 Bearing Cover |
3 、 Bearing | 4 、 Bearing body |
5 、 Sleeve | 6 、 packing gland |
7 、 Sealing machine | 8 、 Suction casing |
9 、 Wearing ring | 10 、 Impeller |
11 、 Midsegment | 12 、 Balance pipe |
13 、 Discharge casing | 14 、 Balancing ring |
15 、 Balancing disk | 16 、 End cover |
17 、 Sleeve | 18 、 Tightening |
19 、 Pump shaft | 20 、 Round nut |
The directions of suction and discharge of the pump are all vertical and upward .with different stages selected according to the needed head.
Stator of the pump is composed of suction casing .mid-segment.discharge casing .end cover and bearing body.
Rotor of the pump is composed of shaft.impellers.sleeves,and balancing disk,The two ends are supported by the ball-bearings.
Paper gaskets are used on the contacting surfaces between the suction casing.mid-segment and discharge casing of the pump.They are sealed by tightening the bolts. ○ -rings are mounted on the interfaces between the sleeves to prevent water from entering the bearnjngs. ○ ilimmersed machine is sealing at the two ends the pump.
There are water cooling jackets around the bearing housings.when the temperature of liquid is higher than 80 ℃ ,Cooling water should be turned on to cool the bernings.
Calcium grease lubricant is firled into the bearing thrugh oil-cups.Viewing from the direction of the suction casing .the pump is rotating clockwise
Stages | Dimensions | Moto used | ||||||||||||
L | L₁ | Le | L₃ | L₄ | L₅ | L₆ | Lr | H | H₁ | H₂ | B | B₁ | ||
2 3 4 5 6 7 8 9 | 961 1031 1156 1206 1256 1306 1481 1531 | 380 400 475 475 475 475 600 600 | 122.5 172.5 222.5 272.5 322.5 372.5 422.5 472.5 | 59 85 110.5 110.5 171.5 171.5 258.2 258.2 | 736 793 940 940 1040 1040 1266 1266 | 505 538 602 602 663 663 835 835 | 111 135 211 211 250 250 265 265 | 120 170 220 270 320 370 420 470 | 355 363 393 393 393 393 460 460 | 75 75 75 75 75 75 100 100 | 360 360 360 360 360 360 385 385 | 315 343 373 373 373 373 420 420 | 315 315 315 315 315 315 320 320 | Y100L-2 Y112M-2 Y132S1-2 Y132S1-2 Y132Sz-2 Y132S₂-2 Y160M₁-2 Y160M₂-2 |